Fire-rated sliding doors are intended for use inside a building. They are not suitable for outdoor use or situations where the interior and exterior are connected. These doors are often used in protected escape routes, but may not be used as a direct escape route. These sliding doors can only be installed in the reveal, i.e. in or directly on the wall opening. For proper and safe installation, it is important that the substrate is suitable. Permitted substrates include aerated concrete, cellular concrete, sand-lime brick, concrete, masonry and steel structures that are fire-resistant coated.

Want to know more? Please contact us.
We try to provide clear information on our website. However, personal advice can offer that little bit extra. Our staff are happy to help you find the right solution. Feel free to contact us for a solution that works for your company. Our contact details can be found on the contact page.
Options, standards and certifications for Fire-rated sliding doors
Certification and standards
Fire-rated sliding doors are CE marked and tested according to several European standards:
- Tested in accordance with EN 1634-1 and EN 1634-3
- classified in accordance with EN 13501‑2
- panels classified in accordance with EN 13501‑1 as fire class B‑s1, d0
- validated cycle test in accordance with C3 (> 50.000 cycli)
- CE marked in accordance with EN 13241 and EN 16034
Application
- only suitable for indoor / indoor situations
- applicable in protected escape routes, not as an escape route
- mounting only possible on the wall / opening
- permissible mounting surfaces include: aerated concrete, sand-lime brick, concrete, masonry, fire-resistant steel construction
Standard configuration
- manually operated
- adjustable speed controller with integrated adhesive magnet 24 V
- gravity self-closing with counterweight
- door leaf constructed from fire-resistant composite panels, thickness 42 mm, with a mixed white structure
Optional features
- smoke resistant according Sa
- rail cap, galvanised steel
- panels in RAL color of choice based on wet painting or wrap foil
- galvanised steel parts powder coated in RAL colour of your choice
- free-swing system for operation independent of counter weight
- bediening onafhankelijk van contragewicht
- motor and control box 400 V for electrical opening and closing
- Smoke detector for stand-alone system
classification: EI(1)
Fire resistance: 60 min.
max. opening width: 5.450 mm
max. opening height: 6.750 mm
Max opening: 25 m²
classification: EW
Fire resistance: 120 min.
max. opening width: 5.450 mm
max. opening height: 6.750 mm
Max opening: 25 m²